CYS Series Three-phase Emergency Lighting Power Supply
·Description
CYS three-phase EPS adopts the modern power electronic conversion, frequency conversion technology, with the latest intelligent IGBT module and CPU controlled digital products. It has a complete protection function, reliable and easy to maintain. It can provide the second line of emergency power for the important electrical equipment, fire-fighting devices and fire emergency lighting etc. As the increasing of the fire protection ability, the emergency light resources has become a necessary fire protection equipment.
·Application Field
It is ideal for the power supply or emergency lighting of various construction, medicine, traffic, financial, office, shopping mall, schools, dock, square and other places.
·Features
■Centralized power supply mode and doesn’t need any special lights;
■CPU control, pure sine wave output;
■Intelligent IGBT module guarantees the stable output balance;
■Smart monitor and firefighting via RS232;
■LCD, LED display, sound and light alarm, easy maintenance;
■No noise, no smoke, pollution-free, no fire hazards;
■Unattended automatic switching;
■Energy saving, basically no power consummation in normal times;
■Stable performance, safe and reliable and it has a long service life;
■Wide application. It can provide emergency lighting for personnel evacuating, fire protection and rescue and other emergency situations;
■Its comprehensive cost is low compared with the generator set and has a high cost performance.
Model
|
CYS
2.2KW
|
CYS
3.7KW
|
CYS
5.5KW
|
CYS
7.5KW
|
CYS
11KW
|
CYS
15KW
|
CYS
18.5KW
|
CYS
22KW
|
Power
|
2.2KW
|
3.7KW
|
5.5KW
|
7.5KW
|
11KW
|
15KW
|
18.5KW
|
22KW
|
Input | ||||||||
Voltage
|
Three-phase 380V±25% Single-phase 220V±25%
|
|||||||
Phase
|
Three-phase four-wire + PE
|
|||||||
Frequency
|
50Hz±5%
|
|||||||
Output
|
||||||||
Voltage
|
In normal as same as the mains voltage in emergency: 380V±3%
|
|||||||
Frequency
|
In normal as same as the mains frequency in emergency: 50Hz±0.5%
|
|||||||
Waveform
|
Sine Wave
|
|||||||
Output Routes
|
According to the design requirements, to make the output loop
|
|||||||
Battery
|
||||||||
Type
|
Maintenance-free sealed Lead-Acid battery with suspended electrolyte: leak proof
|
|||||||
Rated Voltage
|
216VDC
|
DC324VDC
|
||||||
Charging Voltage
|
258VDC
|
368VDC
|
||||||
Charge Current
|
3A
|
7A
|
||||||
Charging Time
|
<20h
|
|||||||
System
|
||||||||
Transfer Time
|
<0.25s (according to the important occasion, it can be set the switch time to 0ms)
|
|||||||
Emergency Time
|
90min (according to the requirement)
|
|||||||
Overload
|
120% / 150% overloads can maintain 60 minutes / 5 seconds.
|
|||||||
Protection
|
Under voltage, over current, short circuit protection
|
|||||||
Noise
|
In normal without noise; in emergency < 50dB (1m away)
|
|||||||
Display
|
LED, LCD
|
|||||||
Efficiency
|
In emergency power supplying: ≥92% In normal: ≥99%
|
|||||||
Environment
|
||||||||
Humidity
|
0~90% ( non-condensing)
|
|||||||
Temperature
|
-25℃~40℃
|
|||||||
Elevation
|
≤2500m
|
|||||||
Adapted Loads
|
Applicable to all kinds of the lighting loads
|
|||||||
Physical Feature
|
||||||||
Open-up and In-line
|
Single front door open, double-open back door, in/out lines of the bottom
|
|||||||
Battery Cabinet
|
Batteries in the host cabinet
|
1
|
||||||
Size(mm)
(W*D*H)
|
750*410*1200
|
800*600*2200
|
||||||
Host EPS Weight(kg)
|
180
|
360
|
720
|
860
|
1030
|
230
|
260
|
280
|
Battery Weight (kg)
|
-
|
-
|
-
|
-
|
-
|
1120
|
1120
|
1580
|
Model
|
CYS
30KW
|
CYS
37KW
|
CYS
45KW
|
CYS
55KW
|
CYS
75KW
|
CYS
93KW
|
CYS
110KW
|
CYS
132KW
|
Power
|
30KW
|
37Kw
|
45KW
|
55KW
|
75KW
|
93KW
|
110KW
|
132KW
|
Input | ||||||||
Voltage
|
Three-phase 380V±25%/ Single-phase 220V±25%
|
|||||||
Phase
|
Three-phase four-wire + PE
|
|||||||
Frequency
|
50Hz±5%
|
|||||||
Output
|
||||||||
Voltage
|
In normal as same as the mains voltage; in emergency: 380V±3%
|
|||||||
Frequency
|
In normal as same as the mains frequency; in emergency: 50Hz±0.5%
|
|||||||
Waveform
|
Sine Wave
|
|||||||
Output Routes
|
According to the design requirements, to make the output loop
|
|||||||
Battery
|
||||||||
Type
|
Maintenance-free sealed Lead-Acid battery with suspended electrolyte: leak proof
|
|||||||
Charging Time
|
<20h
|
|||||||
System
|
||||||||
Transfer Time
|
<0.25s (according to the important occasion, it can be set the switch time to 0ms)
|
|||||||
Emergency Time
|
90min (according to the requirement)
|
|||||||
Overload
|
120% / 150% overloads can maintain 60 minutes / 5 seconds.
|
|||||||
Protection
|
Under voltage, over current, short circuit protection
|
|||||||
Noise
|
In normal without noise in emergency < 50dB (1m away)
|
|||||||
Display
|
LED、LCD
|
|||||||
Efficiency
|
In emergency power supplying: ≥92% In normal: ≥99%
|
|||||||
Environment
|
||||||||
Humidity
|
0~90% ( non-condensing)
|
|||||||
Temperature
|
-25℃~40℃
|
|||||||
Elevation
|
≤2500m
|
|||||||
Adapted Loads
|
Applicable to all kinds of the lighting loads
|
|||||||
Physical Feature
|
||||||||
Open-up and In-line
|
Single front door open, double-open back door, in/out lines of the bottom
|
|||||||
Battery Cabinet
|
2
|
3
|
4
|
5
|
6
|
|||
Size(mm)
(W*D*H)
|
800*600*2200
|
1000*800*2200
|
||||||
Host EPS Weight(kg)
|
320
|
380
|
410
|
470
|
600
|
900
|
1000
|
1200
|
Battery Weight(kg)
|
1580
|
2240
|
3160
|
3160
|
4740
|
6320
|
6320
|
7900
|
Model
|
CYS
160KW
|
CYS
187KW
|
CYS
200KW
|
CYS
220KW
|
CYS
250KW
|
CYS
280KW
|
CYS
315KW
|
CYS
400KW
|
Power
|
160KW
|
187Kw
|
200KW
|
220KW
|
250KW
|
280KW
|
315KW
|
400KW
|
Input | ||||||||
Voltage
|
Three-phase 380V±25%/ Single-phase 220V±25%
|
|||||||
Phase
|
Three-phase four-wire + PE
|
|||||||
Frequency
|
50Hz±5%
|
|||||||
Output
|
||||||||
Voltage
|
In normal as same as the mains voltage; in emergency: 380V±3%
|
|||||||
Frequency
|
In normal as same as the mains frequency; in emergency: 50Hz±0.5%
|
|||||||
Waveform
|
Sine Wave
|
|||||||
Output Routes
|
According to the design requirements, to make the output loop
|
|||||||
Battery
|
||||||||
Type
|
Maintenance-free sealed Lead-Acid battery with suspended electrolyte: leak proof
|
|||||||
Charging Time
|
<20h
|
|||||||
System | ||||||||
Transfer Time
|
<0.25s (according to the important occasion, it can be set the switch time to 0ms)
|
|||||||
Emergency Time
|
90mins (according to the requirement)
|
|||||||
Overload
|
120% / 150% overloads can maintain 60 minutes / 5 seconds.
|
|||||||
Protection
|
Under voltage, over current, short circuit protection
|
|||||||
Noise
|
In normal without noise; in emergency <50dB (1m away)
|
|||||||
Display
|
LED、LCD
|
|||||||
Efficiency
|
In emergency power supplying: ≥92% In normal: ≥99%
|
|||||||
Environment
|
||||||||
Humidity
|
0~90% ( non-condensing)
|
|||||||
Temperature
|
-25℃~40℃
|
|||||||
Elevation
|
≤2500m
|
|||||||
Adapted Loads
|
Applicable to all kinds of the lighting loads
|
|||||||
Physical Feature
|
||||||||
Open-up and In-line
|
Single front door open, double-open back door, in/out lines of the bottom
|
|||||||
Battery Cabinet
|
7
|
8
|
9
|
10
|
12
|
13
|
||
Size(mm)
(W*D*H)
|
1000*800*2200*2 sets
|
800*1200*2200
*2 sets
|
||||||
Host EPS Weight (kg)
|
180
|
360
|
720
|
860
|
1030
|
230
|
260
|
280
|
Battery Weight (kg)
|
-
|
-
|
-
|
-
|
-
|
1120
|