Hpower Series
·Description
HPower featured 3-in 3-out UPS power is specially designed for critical medium and large systems, such as data processing centers, communications systems, and enterprise equipments. It provides a stable power environment and reliable power protection to meet the requirements of high reliability and high-power UPS of the users. The innovative design makes this series with unparalleled reliability and high-performances. The high input power factor and low input current distortion rate make it the green and environmental-protected product. The high efficiency grantee the energy saving efficiency. Advanced control technology enable up to 6 set directly run in parallel. UPS monitoring software can achieve communication between the UPS and the PC through the RS232 interface and allow users to understand the contents of the working status and the history of the UPS. Optional SNMP card makes network remote monitoring and management possible, which is truly unattended. Hpower Series UPS is your best choice!
·Application
Servers, data networks and internet service provider in telecommunication, finance, insurance, government, transportation and medical labs.
·Features
■ SPWM pulse width modulation IGBT power module output isolation transformer (optional), ensuring that the output is unaffected by power grid fluctuations and noise interference;
■ DSP all-digital control all processes of rectifier, inverter, charge and discharge power conversion;
■ Digital circulation technology, small circulation, and raise the reliability of the overall parallel system;
■ Wide input voltage and frequency range, adapting to harsh grid environment and accessible to generator;
■ The input power factor up to 0.99, the input harmonic current of less than 3%, the whole greater than 95% efficiency, environmental-protection, energy-efficient;
■ Under-voltage/ over-voltage protection, overload protection, short circuit protection, over temperature protection, battery low voltage alarm/protection, battery over charge/discharge protection, and so on;
■ Full Frontal maintenance, supporting up and down into the line way, saving installation space;
■ Modular design for subsystem easy on-site maintenance;
■ Internal manual maintenance bypass further improve the reliability of load continuous operation up to 200,000 hours, MTBF, MTTR 30 minutes;
■ System fan take redundancy design, and greatly improve the reliability of the system;
■ Standard input anti-lightening board (optional) and enhance the anti-jamming capability;
■ Intelligent battery management (ABM) extends battery life and reduces the maintenance;
■ State-of-the-art automatic constant current and voltage conversion charging technology maximize the activation of the battery charger to save time, thus extending the service life of the battery;
■ High operating efficiency reduces the running costs of the machine, the design of this series allows the user to select the line and the economy / bypass operation mode, economy / bypass operating mode operating efficiency can reach 99%, thus greatly reducing operating costs and extending battery life;
■ Insert and machine module (optional) can be up to six run in parallel ,which increases the reliability and scalability of the system ;
■ Self-diagnostic function avoid UPS hazards that may lead to the risk of failure;
■ Intelligent system self-diagnostics program, a rich record of failure, capacity history of storage space;
■ Friendly interface design, configuration, with large-screen LCD touch screen and control the keyboard, ensuring users to accurately display the UPS work environment and working conditions;
■ Through RS232, RS485 interfaces with the monitoring software users being able to communicate with a computer. The various parameters of the UPS can be displayed on communication interfaces;
■ The configuration of the SNMP card and monitoring
software, using TCP/IP, SNMP, HTTP, TFTP, through the WEB browser, to achieve
in the Internet/ Intranet remote monitoring, real-time status query,
information management, remote control, parameters settings, user managements,
historical data query comprehensive monitoring and management functions, and
can send short message or Email to users to alarm through mobile phones or
system administrators, support for the operating systems: Windows 7, Unix,
Linux etc.
·Technical Specifications
Model |
HP10 |
HP15 |
HP20 |
HP30 |
HP40 |
HP60 |
HP80 |
HP100 |
HP120 |
HP160 |
HP200 |
HP400 |
|
Capacity |
10KVA |
15KVA |
20KVA |
30KVA |
40KVA |
60KVA |
80KVA |
100KVA |
120KVA |
160KVA |
200KVA |
400KVA |
|
Input |
|||||||||||||
Voltage |
380/400/415VAC(228~518VAC) |
||||||||||||
Voltage Range |
-40%~25% (input voltage from -20%-40% linear decline, power from 100%-70% linear decline) |
||||||||||||
Frequency |
40~70Hz |
||||||||||||
Power Factor |
>0.99 |
||||||||||||
Soft Start |
60s |
||||||||||||
Current Distortion |
<3% |
||||||||||||
Max Input Current |
15 |
23 |
30 |
45 |
60 |
90 |
120 |
150 |
180 |
240 |
300 |
600 |
|
Bypass |
|||||||||||||
Voltage |
380/400/415VAC |
||||||||||||
Voltage Range |
-20% ~ +15% |
||||||||||||
Frequency |
50/60Hz |
||||||||||||
Frequency Range |
±3Hz(±15% adjustable) |
||||||||||||
Inverter/Bypass Transfer Time |
Synchronous switching: ≤ 1ms; uninterrupted switching: ≤ 10ms |
||||||||||||
Overload |
<135% long-term work;135%~150% maintain 1minute then shutdown;>150% maintain 300ms then shutdown |
||||||||||||
Output |
|||||||||||||
Voltage |
380/400/415VAC |
||||||||||||
Voltage accuracy |
±1%(load balancing), ±1.5%(unbalanced load) |
||||||||||||
Frequency |
50/60Hz±0.01% |
||||||||||||
Voltage distortion rate |
THD<1% (linear load), the THD<3% (nonlinear) |
||||||||||||
Phase Voltage |
220V |
||||||||||||
Peak |
3:1 |
||||||||||||
Waveform |
Sine Wave |
||||||||||||
Waveform Distortion |
±1% |
||||||||||||
Three Phase of Precisions |
120°± 0.5° |
||||||||||||
Power Factor |
0.9 |
||||||||||||
Steady-state voltage Stability |
±0.5% (Load balancing) |
||||||||||||
Transient Voltage Response |
In 20ms, restored to ±1% output voltage |
||||||||||||
Overload |
105% long-term work;110%/125%/150% maintain 1hour/10minutes /1minute then switch to bypass;>150% maintain 200ms then switch to bypass |
||||||||||||
Battery Power Switching Time |
0ms |
||||||||||||
Bypass Inverter Time |
0ms |
||||||||||||
MTBF |
≥200,000hrs |
||||||||||||
Dynamic Voltage Transients |
<5% (0~100% load) |
||||||||||||
Voltage Unbalance (100% load unbalancing) |
±3% |
||||||||||||
Frequency Tracking Rate |
0.1 Hz/s-5Hz/s,adjustable |
||||||||||||
Battery |
|||||||||||||
Type |
Sealed maintenance free lead acid battery |
||||||||||||
Voltage |
±240VDC (32~44 can be set) |
||||||||||||
Charging Settings |
Intelligent dynamic adjustment; Amperage is(20%*System Capacity)/Voltage |
||||||||||||
Voltage Stability |
±1% |
||||||||||||
System |
|||||||||||||
System Efficiency |
Normal Mode: 95%,Economic Mode: 98% |
||||||||||||
Battery Mode Efficiency |
>96% |
||||||||||||
Display |
LCD+LED + keyboard |
Display |
|||||||||||
Wiring |
Up and down wiring |
||||||||||||
Optional |
SNMP network communication card, Parallel component , lightning protection module, battery temperature compensator, message alarm, dust-proof net,LBS |
||||||||||||
Environment |
|||||||||||||
Working Temperature |
0~40℃ |
||||||||||||
Storage Temperature |
-10℃~40℃ |
||||||||||||
Relative Humidity |
0~95%( non-condensing) |
||||||||||||
Altitude |
≤1000 m;>1000 m,de-rating according to GB/T 3859.2 |
||||||||||||
Noise(dB) |
<55dB |
||||||||||||
Communication |
|||||||||||||
Ports |
RS232、RS485,contracts,optional SNMP card, Generator interface |
||||||||||||
Control Board |
EPO |
||||||||||||
Protection |
|||||||||||||
EMI |
IEC62040-2 |
||||||||||||
EMS |
IEC61000-4-2(ESD), IEC61000-4-3(RS) IEC61000-4-4 (EFT), IEC61000-4-5 (Surge) |
||||||||||||
Insulation Resistance |
>2M (500VDC) |
||||||||||||
Dielectric Strength |
(Input and output to ground) 2820Vdc. The leakage current is less than 3.5mA 1 minute without flashover |
||||||||||||
Surge Protection |
Complied with VI of IEC60664-1, can withstand 1.2/50us +8 / 20us mixed wave capacity of not less than 6KV/3KA |
||||||||||||
Protection Level |
IP21 |
||||||||||||
Standard |
|||||||||||||
Safety standard |
EN62040-1 |
||||||||||||
EMC |
EN62040-2,EN61000-4-2,EN61000-4-3,EN61000-4-4,EN61000-4-5,EN61000-4-6 |
||||||||||||
Produce |
YD/T1095-2018 |
||||||||||||
Physical Feature |
|||||||||||||
Weight(kg) (internal/external) |
87/43 |
97.5/46 |
90/46 |
107/60 |
116 |
170 |
210 |
210 |
266 |
305 |
350 |
810 |
|
Size(W*D*H, mm) |
540*690*1100 Built-in type |
540*690*1100 Built-in type |
540*764 *1100 |
600*980 *950 |
600*980 *1150 |
600*980 *1400 |
650*960 *1600 |
1300*1100 *2000 |
|||||
280*731*668 External type |
320*781*788 External type |