LSTS Series
·Description
■Design and manufactured under power standard requirements;
■Synchronous control technology and high-speed sampling modules to ensure the synchronous transfer time;
■MCU digital control with intelligent detection and monitoring function;
■SCR module design with strong impact resistance and overload;
■Topological convergence delay structure to achieve the accuracy of switching time;
■Strong compatible with same phase and different phase synchronously;
■Full protection of over voltage, under voltage and overcurrent;
■LCD and LED operation and monitoring display;
■Real-time monitoring on PC via RS232;
·Technique Specifications
Models
|
LSTS
25A
|
LSTS
32A
|
LSTS
40A
|
LSTS
63A
|
LSTS
100A
|
LSTS
160A
|
LSTS
250A
|
LSTS
400A
|
LSTS
600A
|
LSTS
800A
|
Capacity
|
16.5KW
|
21KW
|
26KW
|
41.5KW
|
66KW
|
105.6KW
|
165KW
|
264KW
|
396KW
|
528KW
|
Rated Current
|
25A
|
32A
|
40A
|
63A
|
100A
|
160A
|
250A
|
400A
|
600A
|
800A
|
Transfer Time
|
≤6ms
|
|||||||||
Transfer Method |
Automatic, manual
|
|||||||||
Priority |
configurable
|
|||||||||
Output Interface
|
Copper
|
|||||||||
Input
|
||||||||||
Voltage
|
M1 342V-420V±5V; M2 342V-420V±5V
|
|||||||||
Frequency
|
50HZ、60HZ
|
|||||||||
Environment
|
Same phase, different phase
|
|||||||||
Output
|
||||||||||
Voltage
|
342V~420V±5V
|
|||||||||
Over Current
|
110%
|
|||||||||
Efficiency
|
≥98%
|
|||||||||
Environment
|
||||||||||
Cooling
|
Air
|
|||||||||
Max Temperature
|
<60℃
|
|||||||||
Temperature
|
0~40℃
|
|||||||||
Humidity
|
10%~90% (Non-condensing)
|
|||||||||
Elevation
|
<1000m
|
|||||||||
Physical Feature
|
||||||||||
Size (W*D*H,mm)
|
380×600×800(Rack-mountable)
|
1000*600*1800(Rack-mountable)
|
Products shall be subject to any changes without additional notices. The pictures are for reference only. Please adhere to the original products in case of any mistake!